Power,for Variable Frequency Drivers

Power 1,8/3 kV

(for Variable Frequency Drives)

halogen free - flame retardant

electromagnetic shield – armoured

operating temperature over 100 °C

(see page 6)

Design and construction

IEC 60092-353

Nominal voltage  Uo / U

1,8/3 kV (Umax   3,6 kV)

Operating voltage rate Uo/U

0,6/1 kV

Max. operating voltage Umax

1,2   kV

Maximum rated temperature

90° C  according to IEC 60092-360

Flame retardancy

IEC 60332-1-2             IEC 60332-3-22 Cat A

Halogen content & corrosivity

IEC 60754-1 / 2             IEC 60684-2

Smoke density

IEC 61034-1 / 2

Toxicity & smoke density

IMO RESOLUTION MSC 41(64)

Weather (UV) resistance

UL 1581 § 1200

Ozone resistance

IEC 60092-360  

ElectroMagnetic Compatibility

IEC 60533

Cold bend and Impact test (- 40° C)

CSA C 22.2 N° 0.3-01 & N° 38-05

 

Construction Data

 

1 CONDUCTOR

plain or tinned annealed copper flexible Class 2 or

                                                       Class 5   IEC 60228

2 INSULATION

XLPE HF compound                        IEC 60092-360

3 EARTH CONDUCTORS

plain or tinned copper flexible Cl 2, XLPE sheathed  

4 BEDDING

FLAMEBAR® fiberglass tape(s) (*) + fiberglass  

ropes, XLPE sheathed (when sect. ≥ 10 mm²)

5 INNER SHEATH

HF thermoplastic compound

6 ELECTROMAGNETIC SHIELD

plain copper tape (*)

7 ARMOUR

plain or tinned copper or galvanized steel wire braid

8 OUTER SHEATH

SHF1 or SHF2 compound                 IEC 60092-360

                                                              separator polyester tape s (*) where necessary

                                                            (*) tape overlapping ≥ 50 %

 

Cores Identification

3 cores

black light blue      brown

earth        

green / yellow

 

Sheath colour

black (other colours on request)

 

Sheath marking

CCI XAI VFD EMC   1,8/3 kV  n x sect mm²        IEC 60092-353

IEC 60332-3-22 Cat A meter marking   year    QA n°

 

  • Minimum Bending Radius: 4D (Overall Diameter) – see Generals section

 

APPROVED BY;
approvals
REQUEST INFORMATION:

This email address is being protected from spambots. You need JavaScript enabled to view it.

150 / 250 V

CONSTRUCTION

CONDUCTOR

DIAMETER

nominal

  INSULATION

THICKNESS

nominal

DIAMETER

 UNDER ARMOUR

nominal

OVERALL

DIAMETER

approx

WEIGHT

approx

CONDUCTORS

EARTHS

n

 

[mm²]

n

 

[mm²]

[ mm ]

[ mm ]

[ mm ]

[ mm ]

[ kg/km ]

3

x

50

3

x

10

8,4

2,5

40,6

,,

49

4.050

3

x

70

3

x

16

10,0

2,5

44,3

53

5.060

3

x

95

3

x

16

11,8

2,5

48,2

57

6.130

3

x

120

3

x

25

13,2

2,5

51,2

60

7.220

3

x

150

3

x

25

14,6

2,5

54,2

63

8.200

3

x

185

3

x

35

16,5

2,5

58,4

67

9.920